HD-6 Hydrogen Detector
Designed for continuous hydrogen monitoring in Battery Energy Storage System (BESS) applications
The long-life, low-maintenance Macurco HD-6 Hydrogen Gas Detector is designed for continuous hydrogen monitoring in Battery Energy Storage System (BESS) applications. In the event of battery failure, combustible gas leaks can create unstable conditions that may escalate into explosion risks. To protect personnel and assets, the HD-6 Gas Detector features two configurable alarm levels with relay activation for early warning and response. Standard features include local audible alarming, visual indicators, and analog communication for seamless integration with Building Management Systems (BMS).- UL 2075 & CAN/ULC 588 Listed
- UL 2075 Listed
- 10-year sensor life
- Minimal maintenance required
- 5 A SPDT fan relay, 0.5A alarm relay to control fans, valves, louvers, horn and strobes
- Sensor Range: 0-50% LEL Hydrogen
- Easy installation to 4x4 electrical boxes via mud plate
- 12 to 24 VAC or 12 to 32 VDC
- LED display to show gas concentrations easily
- 4-20mA output to control VFDs and send to BMS
- End of life notification
- Works with Macurco digital control panels
| Size | 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm) |
| Shipping Weight | 1 pound (0.45 kg) |
| Voltage/Current | Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC |
| Current Draw | Current @ 24 VDC: 75 mA in alarm, 50 mA fan relay on and 23 mA stand by |
| Signal | Analog: 4-20mA MRS-485: Digital Modbus adapter BRS-485: BMS communication |
| Relays | 5A Fan relay & 0.5A alarm relay User adjustable settings |
| Buzzer Rating | 75 dBA at 10 Ft |
| Visual Indicator | Green status LED |
| Operating Temperature | -22°F to 158°F (-30°C to 70°C) |
| Ambient Humidity | 10-90% RH non-condensing |
| Warranty | Two year limited warranty |
| Life Expectancy | 10 years with EOL notification |
| Certifications | Certified to UL 2075 |
| Panel Compatibility | DVP-1200, DVP-120M, DVP-120B (Hydrogen Only) |
- Energy Storage Containers
- Data Center
- Charging Station
- Solar Farm
- Power Station
- Renewable Energy
- Demand Response
- Grid Services
MacurcoDVP-1200
Gas detectors provides automatic control to help maintain an acceptable environment in parking garages or other applications
Buy now!$4,102.00 USDNormally ships in 2-3 weeks
MacurcoDVP-120 Detection Ventilation Control Panels
Designed to meet specifications for safety in enclosed parking garages, including the uniform building code & OSHA 50ppm CO...
Starting at$2,145.00 USDNormally ships in 3-4 weeks
MacurcoMRS-485 Addressable Adapter
Converts the 4-20mA analog signal from Macurco 6-Series type detectors to a digital signal for use w/ multipoint addressable systems
Buy now!$178.00 USDNormally ships in 3-4 weeks
MacurcoBRS-485
An accessory used to convert the 4-20mA analog signal from Macurco 6-Series type detectors to a digital signal
Buy now!$320.00 USDNormally ships in 2-3 weeks
MacurcoHS Horn & Strobe Series
Devices use low current to provide a high decibel output & can be easily seen & heard from afar
This product is no longer available. Contact us at 800-567-8686 for alternative solutions.
MacurcoDMK-1 Duct Mounting Kit
Airtight enclosure that provides a means to mount any Macurco gas detector to an air duct
Buy now!$285.00 USDNormally ships in 3-4 weeks
MacurcoWHK-1 Weatherproof Housing Kit
Weather-proof enclosure that provides means to protection-mount all Macurco 6-Series gas detectors in non-hazardous locations
Buy now!$276.00 USDNormally ships in 3-4 weeks
MacurcoPS-24 Plug-In Adaptor
Plug in adaptor for 6 series, horn and strobe, CM-E1, GD-2B
Starting at$61.00 USDNormally ships in 2-3 weeks