Skip to main content
Press Enter
DGH

DIN-130 Thermocouple Input Modbus Modules

Convert analog input signals to digital data and transmit via RS-485 using the Modbus RTU protocol for communication

This product is no longer available. Contact us at 800-567-8686 for alternative solutions.

Have questions? We're here to help!
Have questions? We're here to help!

The DIN-130 thermocouple input Modbus modules convert analog input signals to digital data and transmit via RS-485 using the Modbus RTU protocol for communication.  The modules provide a wide variety of ranges and perform all signal conditioning, scaling, thermocouple linearization and conversion to either linearized ASCII data values or Modbus percent of full scale binary values.

TypesJ, K, T, E, R, S, B, C (Factory Set)
Accuracy (errors from all sources) from 0 to +40°C ambient+/- 1°C max (J,K,T,E types). +/- 2.5°C max for (R,S,B,C types)
Resolution1°C
Common Mode Rejection100 db at 50/60 Hz.
Lead Resistance Effect< 20 µV per 350 Ω
Input Burnout ProtectionTo 250 VAC
Input Impedance100 MΩ min.
IndicationsOpen thermocouple indication
Overrange indication
Thermocouple Measurement RangesJ = -200 to +760°C
B = 0 to +1820°C
K = -150 to +1250°C
S = 0 to +1750°C
T = -200 to +400°C
R = 0 to +1750°C
E = -100 to +1000°C
C = 0 to +2315°C

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more