The D6000 series modules are a complete family of data acquisition modules for use in process control systems. These modules can measure process signals such as thermocouples, 4-20mA current loops, discrete contact closures, and they can generate voltage or current signals for controlling annunciators or valves. Complete data acquisition systems can be created with ease with the D6000 modules and a host supervisory computer or programmable logic controller.

The modules provide direct connection to a wide variety of sensors and annunciators. They perform all signal conditioning and linearization and contain no pots or DIP switches. All user-selectable settings, such as ranges, communications settings are stored in nonvolatile EEPROM, which maintains these values even after power is removed. 

The D6000 series modules can be connected to an Ethernet network using a serial to ethernet converter..

The D6000 series ADC modules can also be mounted on a DIN-Rail using the MK-1 mounting kit.

The D6000 series remote I/O modules are compatible with all commercial  software programs and OPC servers that support the Modbus RTU protocol. Commercials software programs from DreamReport, Wonderware, National Instruments Labview, Indusoft, DAQFactory and  Dasylab all support the Modbus RTU protocol. OPC Servers from  Kepware and MatrikonOPC support the Modbus RTU protocol.

• Build complete data acquisition systems
• Analog and Digital I/O models available
• User-selectable analog input range per channel
• RS-485 serial communications interface
• Modbus RTU Protocol
• Differential Analog Inputs
• 500Vrms analog input or analog output isolation
• 16-bit analog input measurement resolution
• Continuous self-calibration
• No adjustments required
• Programmable analog input digital filters
• Requires +10V to +30Vdc unregulated supply
• Transient suppression on RS-485 data lines
• Removable screw terminal plug connectors
• CE marked
 

D6500 Analog Outputs• Two analog outputs
• Programmable voltage or current ranges
• Voltage Ranges: 0-10 VDC, +/- 10 VDC
• Current Ranges: 0-20 mA, 4-20 mA
• 250 conversions per second
• Accuracy: +/- 0.1%
• 12-bit DAC resolution
• Span Tempco: +/- 25 ppm/°C max.
• Settling Time to 0.1% FS: 1 mS
• Communications Watchdog Timer
• Current Output Compliance: +/- 12 VDC
• Voltage Output Drive: 5 mA max.
• 8-bit ADC Analog output signal readback
• Isolation 500 VAC, output common to system ground
• Current output burnout protected to 250 VAC
• Power requirements: Serial = 2.1 W
D6710 Digital Inputs• 15 Digital Inputs
• Internal 10K pull-up resistors on each bit
• Accept direct switch closure
• Logic “0” = < 1 VDC, Logic “1” = > 3.5 VDC
• Input burnout to +/- 30 VDC without damage
• Isolation 500 VAC, input common to system ground
• Power requirements: Serial = 0.75 W
D6720 Digital Outputs• 15 Open-collector outputs to 30 VDC, 100 mA max.
• VSat: +0.3 VDC max. at 100 mA.
• Short circuit protection to 500 mA.
• Communications Watchdog Timer
• Digital Output update rate, 4.5 Hz
• Isolation 500 VAC, output common to system ground
• Power requirements: Serial = 1.0 W
D6100 Voltage Inputs• Seven differential voltage inputs
• Ranges: +/- 0.025 V, +/- 0.05 V, +/- 0.1 V, +/- 1 V, +/- 5 V, +/- 10 V
• 16-bit ADC, 25/20 conversions per second
• Accuracy: +/- 0.05% of FS max.
• Span Tempco: +/- 50 ppm/°C max.
• Input burnout protection to 250 VAC
• Input impedance: 20 MW min.
• Power requirements: Serial = 1.4 W
D6200 Current Inputs• Seven differential current inputs
• Range: +/- 20 mA
• 16-bit ADC, 25/20 conversions per second
• Accuracy: +/- 0.05% of FS max.
• Span Tempco: +/- 50 ppm/°C max.
• Voltage drop: 2.0 V max.
• Input Impedance: < 100 Ω (70 typical)
• Power requirements: Serial = 1.4 W
D6300 Thermocouple Inputs• Seven differential thermocouple inputs
• Thermocouple types: J, K, T, E, R, S, B, and C
• Ranges:
- J = -200-760°C R = 0-1750°C
- K = -150-1250°C S = 0-1750°C
- T = -200-400°C B = 0-1820°C
- E = -100-1000°C C = 0-2315°C
• Thermocouple Accuracy (error from all sources) from 0-40°C ambient:
- J, K, T, E = +/- 1.5°C max.
- R, S, B, C = +/- 3.5°C max. (300°C to +F.S.)
• 16-bit ADC, 25/20 conversions per second
• Input impedance: 20 MW min.
• Automatic cold junction compensation
• Lead resistance effect: < 40 mV per 350 W
• Open thermocouple and over range indication
• Input burnout protection to 250 VAC
• Power requirements: Serial = 1.4 W
D6400 Voltage, Thermocouple, Current Inputs• Seven Differential voltage, thermocouple, current inputs
• Specifications equal to D6100, D6200 and D6300 series

• Process monitoring and control
• Remote data logging to any host computer
• Product testing
• Direct connection to PLC

  • Thumbnail of document D6000 Serial Data Sheet 1069
    Download

    D6000 Serial Data Sheet 1069

    Download
  • Thumbnail of document D6000 Quickstart 1070
    Download

    D6000 Quickstart 1070

    Download
  • Thumbnail of document D6000 Users Manual Serial 1071
    Download

    D6000 Users Manual Serial 1071

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more