Skip to main content
Press Enter
Starting at $2,194.09USD
Configure
Fuji Electric

V6 Series FKD Differential Pressure Transmitter for Remote Seal

Measures differential pressure up to 2,900 psi, for use w/ diaphragm seal, communicates using HART communications protocol.

Starting at
$2,194.09USD
Have questions? We're here to help!
Have questions? We're here to help!
Configure

 The Fuji Electric V6 Series FKD differential pressure transmitter for remote seal uses a unique micro-capacitive silicon sensor and state-of-the-art digital signal processing to provide exceptional accuracy and stability. The transmitter's silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. Using a silicon measurement diaphragm limits hysteresis and mechanical fatigue problems on the sensitive element, and provides the user with very high zero stability and long-term reliability.

 
The FKD V6 transmitter's advanced floating cell technology protects against temperature variations and overpressure, and substantially reduces the overall measurement error. The burnout current value can be adjusted in the ranges of 3.4 to 3.8 and 20.8 to 22.5 mA, and can be compliant with NAMUR NE43 recommendations. The transmitter's output signal can be linearized using up to 14 points.
 
The electronics unit, local indicators and electronics housing are interchangeable among all FCX-AIV V6 transmitters. Various options are available to address a wide range of process industry applications, including a full range of hazardous area approvals, a built-in RFI filter and lightning arrester, 5-digit local display with engineering units, stainless steel electronics housing, and a wide selection of wetted part materials. An optional local configurator with three magnetic switches allows the user to configure the transmitter without opening the indicator cover.
• Range 1 to 2,900 psi gauge (3.2 to 200,000 mbar)
• Up to ±0.065% of calibrated span accuracy
• 40ms response time
• ±0.2% of upper range limit stability
• 0.05% of calibrated span linearity
• Process temperature
• -40 to 302°F (-40 to 150°C) for rigid mounting
• 32 to 662°F (0 to 350°C) for capillary design and high temperature filling fluid
• HART 7 communication protocol
• Safety Integrity Level 2 or 3 according to IEC 61508 and IEC 61511 standards
• Hazardous area approvals
• Optional LCD display with 3 magnetic push buttons for contactless configuration
• IP66/IP67 and NEMA 4X
• 5-digit local display
  • Thumbnail of document Fuji FKB FKD FKM V6 Datasheet 18547
    Download

    Fuji FKB FKD FKM V6 Datasheet 18547

    Download
  • Thumbnail of document Fuj V6 Series Manual 1 18548
    Download

    Fuj V6 Series Manual 1 18548

    Download

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more