Skip to main content
Press Enter
OMEGA

TXDIN1630 DIN Rail Universal Input Transmitter w/Push Button User Trim

Universal DIN Rail Transmitter

Have questions? We're here to help!
Have questions? We're here to help!

 The TXDIN1600 Series is a new generation DIN rail mounted temperature transmitter. It has been designed to accept most common process and temperature sensor inputs and provide the user with a standard two wire 4 to 20 mA output signal. Isolation is provided between input and output and all temperature ranges are linear to temperature.

 
Designed for ease of use, our latest USB interface is fitted for quick and easy configuration. Just connect a standard USB cable between the TXDIN1600 and your PC. Using our free configuration software, your PC will automatically upload the existing configuration data and guide you through any changes you wish to make. To further help save time, the TXDIN1600 does not need to be wired to a power supply during the configuration process, it is powered via the USB interface from your PC.
 
The TXDIN1600 is also provided with user push button trim, allowing trim adjustments at both 4 mA and 20 mA. The user trim function can be locked during configuration if not required. The range led indicates out of range input during normal operation, during user trim it is used to indicate the stage of trim.
• Simple Configuration Via USB Port
• Universal Pt100, Thermocouple, mV, mA Input
• Isolated Input
• Push Button User Trim (TXDIN1610 and TXDIN1620)
ProtectionReverse connection and over-voltage protection, max over voltage current 100 mA
HysteresisSet in units
RangesSetpoint programmed on units, covering full range of input
Trip TypeIndividual trips A and B may be set at high or low level, full range setpoint plus adjustable
Contact Rating250 Vac rms @ 1 A; 30 Vdc @ 1 A resistive load
Response Time<500 ms to reach 95% of final value; start up time <3 s
Supply24 Vdc ±5% @ 40 mA max
TypeDual form C relay contacts
TXDIN1630
User TrimRaise and lower buttons, active for offset when output is at offset and span, trim lock option
ProtectionReverse connection and over-voltage protection, max over voltage current 100 mA
Output Drive2 mA driving 5 KΩ @ 10V
Calibration Accuracy±5 mV
Response Time<500 ms to reach 95% of final value; start up time <3 s
Supply15 to 28 Vdc
programmable ranges0 to 10, 0 to 5, 2 to 10, 1 to 5, and 0 to 1V
Type3-wire voltage output with
TXDIN1620
User TrimRaise and lower buttons, active for offset when output is between 3.8 to 6 mA, span between 18 to 22 mA, trim lock option
Loop EffectsLoop ripple 0.03% of FSR; supply sensitivity 0.05 uA/°C; supply ripple rejection Protection: Reverse connection and over-voltage protection, max over voltage current 100 mA
Calibration Accuracy±5 uA
Response Time<500 ms to reach 95% of final value; start up time <3 s
Supply11 to 30 Vdc, 24V nominal giving max loop load of 600 R @ 24V
Type2-wire current sink; signal range 4 to 20 mA; full range 3.8 to 24 mA
TXDIN1610
ColorGray Output
Cable2.5 mm (0.1") max
Self Extinguishing TerminalsScrew terminal
MaterialPolmide 6.6
Dimensions17.5 W x 56.4 L x 90 mm H (0.7 x 2.2 x 3.5")
ApprovalsCE tested to BS EN 61326
Storage-40 to 85°C (-40 to 185°F)
AmbientOperating -20 to 70°C (-4 to 158°F) 10 to 95% RH non-condensing
IsolationInput to output tested at 500 Vdc