TX12 RTD Head mount Temp. Transmitter w/User Trim

RTD In-Head Temperature Transmitter

Have questions? We're here to help!
Have questions? We're here to help!

 The TX12 head mounted temperature transmitter connects to any standard pt100 resistance sensor and converts the linearized temperature to a 4 to 20 mA signal. The transmitter is a two wire device, and is fully configurable by the user, over a wide temperature range, with the aid of a simple push button. This new TX12 design incorporates additional configuration menus, allowing the user to push button trim the transmitter output at both zero and span, ideal for trimming out sensor errors. The transmitters advanced circuitry guaranties high stability over the wide operating ambient temperature ranges experienced by head mounted devices. One of the transmitters features is the program LED, which provides visual indication of sensor fault when in normal operation and is also used to guide the operator through the simple menus during configuration.

• User Trim—Null Out Sensor Error
• Unique Push Button Configuration Without PC
• High Stability
• Programmable Burnout
Output ConnectionScrew terminal
Maximum Output21.5 mA (in high burnout condition)
Minimum Output3.8 mA (in low burnout condition)
Accuracy(mA output /2000) or 5 uA (whichever is the greater)
Loop Voltage Effect0.2 uA/V
Thermal Drift1 uA /°C
Maximum Output Load[(Vsupply-10)/20]K Ω
(Example: 700 Ω @ 24V)
General Specifications
Update Time500 mS
Response Time1 second
Start Up Time4 seconds (I out < 4 mA during start up)
Warm-Up Time1 minute to full accuracy
Power Supply10 to 30 Vdc
Environmental
Ambient Operating Range-40 to 85°C (-40 to 185°F)
Ambient Storage Temperature-50 to 90°C (-58 to 194°F)
Ambient Humidity Range10 to 90% RH non condensing
Physical
Dimensions43 diameter; 21 mm height (1.7; 0.8")
Weight31 g (0.068 lb) (encapsulated)
Approvals
EMC-BS EN 613261998: Electrical equipment for measurement control and laboratory use
Input
Sensor TypePt100 100 Ω @ 0°C 2 or 3 Wire
Sensor Range-200 to 850°C (-328 to 1562°F)
Sensor ConnectionScrew terminal
Minimum Span25°C (77°F)
LinearisationBS EN 60751(IEC 751) standard/JISC 1604
Measurement Accuracy0.1°C ±0.05% of reading
Thermal Drift25 ppm/°C
Excitation Current<200 uA
Lead Resistance Effect0.002°C/Ω
Maximum Lead Resistance20 Ω per leg
output
Output Type2 wire, 4 to 20 mA current loop
Output Range(4.0 to 20.0) mA
ANNEX AImmunity test requirements for equipment intended for use in industrial locations
ANNEX FTest configurations, operational conditions and performance criteria for transducers with integrated or remote signal conditioning
IEC 61000-4-2Electrostatic discharge
IEC 61000-4-3EM Field
IEC 61000-4-4Transient burst (output)
IEC 61000-4-5Surge (output)
NoteSensor input wires to be less than 3 m to comply.