 The Series PMT2 Particulate Transmitter is designed to measure particulate emission levels from dust collector discharge. Using DC coupled electrostatic induction sensing technology, the transmitter monitors a pA current that is generated as particulate passes near the probe; a 4 to 20 mA signal will vary based on the particulate level. The PMT2 offers 6 sensitivity ranges allowing the user to choose the range that will best fit the application. The range and test selector switch can also be set to output a 4 mA or 20 mA signal to assist with set up or trouble shooting. Averaging time setting can be used to dampen the signal if desired.

• Simple 2-wire installation for PLC and control panels
• Non-stick PTFE coated probe to prevent false readings from moist and conductive dusts, condensate, and dust buildup
• Remote zero calibration helps to decrease maintenance time
Wetted Materials316L SS, silicone, and PTFE.
ServiceAir and compatible gases, any type of particulate conductive or nonconductive.
ComplianceCE, cULus; ATEX Compliant: 2813 II 1 G Ex ia IIB T4 GA (-40°C ≤ Tamb ≤ 63°C) (-40°C ≤ T Process ≤ 120°C) / II 1 D Ex ia IIIC T120°C Da (-40°C ≤ Tamb ≤ 63°C) (-40°C ≤ T Process ≤ 120°C). Type Certificate No.: DEMKO 16ATEX1768 X. ATEX Standards: EN 60079-0:2012/A11:2013; EN 60079-11:2012. IECEx Certified: Ex ia IIB T4 Ga (-40°C ≤ Tamb ≤ 63°C) (-40°C ≤ T Process ≤ 120°C) / Ex ia IIIC T120°C Da (-40°C ≤ Tamb ≤ 63°C) (-40°C ≤ T Process ≤ 120°C). Certificate of Conformity: IECEx UL 16.013X. IECEx Standards: IEC 60079-0: 2011; IEC 60079-11: 2011. UL Listed Intrinsically Safe for Class I, Groups C and D; Class II, Groups E, F and G; Class III; Class I Zone 0 AEx ia IIB T4 Ga; Class I Zone 0 Ex ia IIB T4 Ga.
WeightVaries with length of probe and type of mount.
Averaging Time1 to 360 s (10 selectable options).
Mounting OrientationAny.
Enclosure RatingUL Type 4 (IP66), ATEX/IECEx IP65.
Probe LengthsSee model chart on catalog page.
Process ConnectionSee model chart on catalog page.
Terminal BlockRemovable (16 to 20 AWG wire).
Electrical ConnectionTwo 1/2" female NPT conduit openings.
Power Requirements12 to 28 VDC.
Output Signal4 to 20 mA.
Pressure Limit30 psi (2 bar).
Temperature LimitsAmbient: -40 to 145°F (-40 to 63°C); Process: -40 to 248°F (-40 to 120°C).
Detection Range5 to 5000 pA (6 selectable range options).
Particulate Size0.3 microns and higher.
Accuracy±5% of reading.
EnclosurePowder coated aluminum.

 • Emissions monitoring

• Broken bag detection in dust collectors
• Filter leak or wear detection
• Bin vent monitoring

  • Thumbnail of document DS PMT2 17625
    Download

    DS PMT2 17625

    Download
  • Thumbnail of document PC PMT2 English Only ATEX 17626
    Download

    PC PMT2 English Only ATEX 17626

    Download

Accessories

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more