Skip to main content
Press Enter
OMEGA

PX2300-1BDI High Accuracy, Wet/Wet Differential Pressure Transmitters

-1 to 1 psi, Differential Pressure

Have questions? We're here to help!
Have questions? We're here to help!

 OMEGA’s PX2300 Series high-output, low differential pressure transducers are compatible with most media, from dry air to corrosive liquids. All wetted parts are either stainless steel or elastomer seals. The electronics are housed in a NEMA 4 (IP65) enclosure. A high working pressure and high overpressure ratings ensure dependability in harsh industrial environments. These transducers are ideal for measuring pressure drop across filters and other process devices.

 
• 0.25% Accuracy
• NEMA-4/IP65 Rating
• Wet/Wet Corrosive Environments
• Ideal for Pressure Drop Across Filters
Excitation24 Vdc nominal
Max30 + 0.004 x (loop resistance Ω) Vdc
Min11 + 0.02 x (loop resistance Ω) Vdc
Loop Resistance0 to 1000 Ω
Output4 to 20 mA (2-wire)
Accuracy±0.25% RSS FS at constant temperature (includes linearity, repeatability and hysteresis)
Linearity±0.20% FS
Hysteresis0.10% FS
Repeatability±0.05% FS
Operating Temperature Range-18 to 80°C (0 to 176°F)
Compensated Temperature Range-1 to 65°C (30 to 149°F)
Thermal Zero Effect<±0.02% FS/°F
Thermal Span Effect<±0.02% FS/°F
SensorCapacitive
Maximum Line Pressure250 psig
Maximum Overpressure
High Side1 to 5 psi = 20 x FS, 10 to 25 psi = 10 x FS, 50 psi = 5 x FS, 100 psi = 2.5 x FS
Low Side2.5 x FS (shift recoverable)
The zero will shift slightly when high differential pressure is applied. The shift may be as much as ±10% FS with overpressure applied to the low port. (Other parameters will not shift.) The shift may be recovered by a positive overpressure or if the overpressure is always in one direction, the user may apply this pressure to pre-set the sensor. Subsequent overloads of less pressure will not cause any further shift.
Wetted PartsAir and fluids compatible with 17-4 and 300 stainless steel, FKM, and silicone O-rings
Cavity Volume0.27/0.08' pos./neg. port
CaseNEMA 4 (IP65)
Pressure Port1/4 NPT internal
Electrical ConnectionInternal barrier strip with 22.2 mm (0.875') conduit opening
Response Time50 ms (water)
Weight410g (14.4 oz)