PD8-6060 ProtEX-MAX Explosion-Proof Dual Analog Input Process Meter

Offers all functionality of the PD6060, approved explosion-proof, accepts two inputs; 4-20 mA or 0-5V, 1-5V, etc.

Starting at
$1,718.00USD
Have questions? We're here to help!
Have questions? We're here to help!
Configure

The ProtEX-MAX™ PD8-6060 offers all the functionality of the ProVu PD6060 as a fully FM, CSA, ATEX, and IECEx approved explosion-proof product. It accepts two inputs of either a process current (4-20 mA) or process voltage (0-5V, 1-5V, etc.) signal. It displays these signals on a dual-line, 6-digit Sunbright sunlight readable display. The meter can be customized such that these two inputs are displayed in a variety of ways, including both at the same time with tags or the result of math functions performed on one or both of the inputs. The PD8-6060 includes a 24 VDC power supply to drive the transmitter and can be equipped with up to four internal relays and a 4-20 mA analog output. It can be programmed and operated without opening the housing by using the built-in SafeTouch® through-glass buttons or the RS485 serial communication port with free Modbus® protocol.

               

Quick Overview

• Input: Dual 0-20 mA, 4-20 mA; ±10 VDC (0-5, 1-5, 0-10 V); Modbus PV (slave)
• Display: Dual-line 6-digit, 0.60" (15 mm) & 0.46" (12 mm)
• Case: Smooth die-cast aluminum explosion-proof
• Power: 85-265 VAC or 12-24 VDC option
• Operating Temperature: -40 to 65°C

 

• SunBright Display Standard
• Addition, difference, absolute difference, average, multiplication,division, min of A or B, max of A or B, draw, weighted average, and ratio math functions
• Signal input conditioning for flow & round horizontal tanks
• Multi-pump alternation control
• SafeTouch® through-glass button programming
• Modbus RS-485 serial communications
• Flanges for wall or pipe mounting
• Isolated 24 VDC @ 25 mA transmitter power supply
• Onboard USB and MeterView® Pro programming software

DisplayUpper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs
Display IntensityEight user selectable intensity levels
Display Update Rate5/second (200 ms)
Over RangeDisplay flashes 999999
Under RangeDisplay flashes -99999
Display AssignmentThe Upper and Lower displays may be assigned to process values for Channels A (Ch-A), B (Ch-B), or C (Ch-C), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B,& Ch-C), toggle between Channel & units, show channel gross value (no tare) or toggle net (tare) and gross values, show relay set points, max& min values, or Modbus input. The second display may also be set to show engineering units or be off, with no display.
Programming MethodsFour through-glass SafeTouch buttons, four mechanical buttons behind glass, digital inputs, PC and MeterView Pro software, or Modbus registers.
F4 Digital Input Contacts3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic LevelsLogic High: 3 to 5 VDC; Logic Low: 0 to 1.25 VDC
Noise filterProgrammable from 2 to 199 (0 will disable filter)
Filter BypassProgrammable from 0.1 to 99.9% of calibrated span
RecalibrationAll ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min DisplayMax (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is cycled.
PasswordThree programmable passwords restrict modification of programmed settings.
Non-Volatile MemoryAll programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
Power Options85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
FuseRequired external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
Isolated Transmitter Power SupplyTerminals P+ & P-: 24 VDC ± 10%. Isolated from the input at >500 V. Jumper selectable for 24, 10, or 5 VDC supply (internal jumper J4). All models transmitter supply rated @ 25mA max.
Normal Mode RejectionGreater than 60 dB at 50/60 Hz
Isolation4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Overvoltage CategoryInstallation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
EnvironmentalT6 Class operating temperature range Ta = -40 to 60°C
T5 Class operating temperature range Ta = -40 to 65°C
See LIM8 ProtEX-MAX instruction manual for additional details.
Max Power DissipationPD8 Series: Maximum power dissipation limited to 15.1 W. See PD8 instruction manual for additional details.
ConnectionsRemovable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
EnclosureExplosion-proof die cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Default conduit connections: Four ¾" NPT threaded conduit openings and two ¾" NPT metal conduit plugs with 12 mm hex key fitting installed. Additional conduit opening configurations may be available; verify quantity and sizes on specific device labeling during installation.
MountingFour slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe mounting
Dimensions (W x H x D)6.42" x 7.97" x 8.47" (163 mm x 202 mm x 215 mm)
Weight16.0 lbs (7.26 kg)
USB ConnectionCompatibility: USB 2.0 Standard, Compliant
Connector Type: Micro-B receptacle
Cable: USB A Male to Micro-B Cable
Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit,
Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
Power: USB Port
Warranty3 years parts & labor