Skip to main content
Press Enter
Starting at $1,291.00USD
Configure
Precision Digital

PD2-6060 Helios Dual Analog Input Process Meter

Displays two 4-20 mA inputs, each transmitter is provided with its own 24 VDC transmitter power supply

Starting at
$1,291.00USD
Have questions? We're here to help!
Have questions? We're here to help!
Configure

What sets the Helios apart from other Large Display Meters is its dual line display with super bright LEDs that can be read even in bright sunlight and up to 100 feet away. Based on Precision Digital's popular line of ProVu® digital panel meters, the Helios can satisfy a wide variety of level, flow, temperature, pressure, & weight applications. It is available with models that accept 4-20 mA, thermocouple, RTD, pulse, strain gauge, AC and DC volts and current, and even Modbus®.

Go with the Helios PD2-6060 when you need a large display meter to display two 4-20 mA inputs on one meter. Both of these inputs can be displayed on six full digits and each transmitter is provided with its own 24 VDC transmitter power supply. The PD2-6060 can also perform a variety of math functions on those two inputs, such as computing the difference between them or summing them together.

Input

 

Two (2) 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V


 

Helios Features

• Large 1.80" Digits
• Dual Line Display
• Six Full Digits on Each Line
• Readable From 100 Feet Away
• Superluminous Sunlight Readable Display
• IP65 Rated Field Mountable Enclosure
• Great for Outdoor Use: -40 to 150°F (-40 to 65°C)
• Program the Meter from a PC with Onboard USB and MeterView® Pro

PD2-6060 Features


• Displays Two Process Inputs Simultaneously
• Math Functions Capabilities
• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• Multi-Pump Alternation Control
• Signal Input Conditioning for Flow & Round Horizontal Tank
• Programmable Displays & Function Keys
• 32-Point, Square Root, or Exponential Linearization
• Current Input Protected by Resettable Fuse
• Tare Function

Under RangeDisplay flashes -99999
Display AssignmentDisplay lines 1 & 2 may be assigned to process values for Channels A (Ch-A), B (Ch-B), or C (Ch-C), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between Channel & units, show channel gross value (no tare) or toggle net (tare) and gross values, show relay set points, max & min values, or Modbus input. The lower display may also be set to show engineering units or be off, with no display.
Programming MethodsFour programming buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
DisplayTwo lines with 1.8" (46 mm) high digits, red LEDs; 6 digits per line (-99999 to 999999), with lead zero blanking
Display IntensityEight user selectable intensity levels
Display Update Rate5/second (200 ms)
Over RangeDisplay flashes 999999
Noise FilterProgrammable from 2 to 199 (0 will disable filter)
Filter BypassProgrammable from 0.1 to 99.9% of calibrated span
RecalibrationAll ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min DisplayMax/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
PasswordThree programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
Power Options85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only.
Isolated Transmitter Power SupplyTerminals P+ & P-: 24 VDC ± 10%. 12-24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
Non-Volatile MemoryAll programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
FuseRequired external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Normal Mode RejectionGreater than 60 dB at 50/60 Hz
Isolation4 kV input/output-to-power line; 500 V input-to-output or output-to-P+ supply
Overvoltage CategoryInstallation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
EnvironmentalOperating temperature range: -40 to 150°F (-40 to 65°C); Storage temperature range: -40 to 185°F (-40 to 85°C); Relative humidity: 0 to 90% non-condensing
ConnectionsRemovable and integrated screw terminal blocks accept 12 to 22 AWG wire.
EnclosureUL Type 4X, IP65 rated. Polycarbonate & glass blended plastic case, color: gray. Includes four PG11 through-hole conduit openings, with two factory installed PG11, IP68, black nylon threaded hole plugs with backing nuts.
Wall MountingFour (4) mounting holes provided for mounting meter to wall.
Pipe MountingOptional pipe mounting kit (PDA6260) allows for pipe mounting. Sold separately.
See PD2-6060 manual for instructions
Tightening TorqueRemovable Screw Terminals: 5 lb-in (0.56 Nm)
Digital I/O and RS485 Terminals2.2 lb-in (0.25 Nm)
Overall Dimensions (H x W x D)10.63" x 12.59" x 4.77" (270 mm x 319.7 mm x 121.2 mm)
Weight6.10 lbs (2.76 kg)
UL File NumberUL & C-UL Listed. E160849; 508 Industrial Control Equipment.
USB ConnectionCompatibility: USB 2.0 Standard, Compliant Connector Type: Micro-B receptacle Cable: USB A Male to Micro-B Cable Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit Power: USB Port
Warranty3 years parts & labor

Accessories

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more