MIC 8200 Process Controller

Dual display 1/4 DIN process controller

Have questions? We're here to help!
Have questions? We're here to help!

The dual display Partlow MIC 8200 process controller is a 1/4 DIN single loop unit capable of measuring, displaying, and controlling a process variable in applications such as temperature, pressure, flow, and level.

Most heating outputs are easily tuned using the Partlow MIC 8200's auto tune function, which has several choices for control algorithms and control responses. Control functions, alarm settings, and other parameters are easily entered through the unit's front keypad. All user's data can be protected from unauthorized changes with the Enable mode security system. MIC 8200 controllers have an additional data protection feature in which battery back-up protects against data loss during AC power outages.

The MIC 8200 can control a variety of processes including those requiring simple on-off to dual 4-20mA outputs with full PID, while providing the operator with constant visual indication of process and setpoint. The top display may be programmed to show the process variable or deviation from setpoint. The lower display, when programmed, is keypad selectable to show setpoint 1, setpoint 2, or percent output.

Input to the 8200 is user-configurable to directly connect to thermocouple, RTD, mVDC, VDC, or mADC inputs. Thermocouple and RTD linearization, as well as thermocouple cold junction compensation, are performed automatically by the Partlow MIC 8200 controller. The sensor input is isolated, and the device can be specified to operate on either 115VAC or 230VAC power at 50/60Hz. It is housed in a 1/4 DIN extruded aluminum enclosure suitable for panel mounting and may be surface mounted using an optional adapter.

Options include single or dual 4-20mA output, up to three relay outputs, three types or alarms, remote setpoint input, electric motor modulation, and RS-485 communications. Process value retransmission output is also available.

• 1/4 DIN for easier viewing
• CSA certified, CE, and UL recognized
• Universal input or specified input
• Relay, solid state relay driver, or 4-20mA outputs
• Transmitter Power Supply
• Position Proportioning
• RS-485 Communications
• Remote Setpoint
• Power Supply 90-264VAC or optional 24V AC/DC
 

Thermocouple TypesJ, K, T, R, S, E, B, N, and C
RTD100 ohm (.00385 Ohm/Ohm/C)
Volts0 to 5VDC, 1 to 5 VDC
Milivolts0 to 25mVDC, 0 to 50mVDC,10 to 50mVDC
Milliamps4 to 20mADC, accommodated via the
addition of a shunt resistor
Remote Setpoint0 to 5VDC, 1 to 5 VDC
Sensor Fault DetectionDisplays Hi or Lo for thermocouple or RTD
inputs (10% above or below range) and
sensor break, SnSr. On/Off outputs go off,
proportional outputs go to 0%. Sensor fault
detection is not functional for 0 to 5VDC.
RelaySPST
115VAC: 5.0 A Resistive; 1/8 HP or 250VA
230VAC: 2.5 A Resistive; 1/8HP or 250VA
SSR DriverOpen collector output
Short circuit protected at 100mA maximum
Provides 4VDC at 20mA or 3VDC at 40mA
Current Output4-20mADC into 650 ohms maximum
Digital DisplayFour 7 segment LED's each .36 inches high
Status IndicatorsIndividual LED indictors for Setpoint 1, Setpoint
2, Out 1, Out 2, Manual, Alarm, Degrees F,
Degrees C, or Engineering Units, minus sign for
negative values, Process Value, Percent Output
1, Percent Output 2, and Remote Setpoint
Auto Reset0.0 to 100.0 repeats/minute
Rate0.0 to 10.0 minutes
Cycle Time1 to 240 seconds
Position Prop. Sensitivity0.0 to 50.0%
First Output Position-1000 to 1000 units
Second Output Position-1000 to 1000 units
Measurement Error Limit• Type J, K, T, E, N, C thermocouples
and RTD +/- 0.25% of reading plus
1 degree at 25 C
• Type R, S, B thermocouple
+/- 0.25% of span at 25 C
• mVDC, mADC and VDC +/- 0.25%
of span at 25 C
Ambient Temperature Error0.01% of span per degree C deviation
from 25 C
Scan Rate1 scan per second, 3 scans available
Display ResolutionT/C & RTD: 0.01 or 1 degree
mV & VDC: 0.001, 0.01, 0.1, or 1.0
Auto Reset Windup InhibitAuto reset is disabled when the
process is outside of the proportional
band
Cold Junction CompensationSelf compensation for ambient
temperature. All calibration values are
stored in memory
Noise RejectionNormal mode, 85dB minimum at 60Hz
or greater.
Common mode, 90dB minimum
–24VAC maximum for RTD input,
115VAC maximum for other inputs.
Line Voltage115/230VAC +/- 10% 50/60 Hz
Power Consumption15VA maximum
Operating Temperature0 to 55 C, 32 to 131 F
Storage Temperature-40 to 65 C, -40 to 149 F
Humidity0 to 90% RH, non condensing
Dimensions1/4 DIN front panel, 5.8" deep
Weight3 pounds maximum
Vibration0.5 to 100Hz at 0.5g
Agency ApprovalsUL and CSA
Transmitter Power SupplyProvides up to 40mA @ 24VDC.
Communications TypeRS-485 serial communication port:
Half-Duplex bi-directional comm.
Process Alarm-9999 to 9999 units
Devitation Alarm-3000 to 3000 units
Deviation Band Alarm1 to 3000 units
On/Off Hysteresis0 to 300 units
Proportional Band1 to 3000 units
Manual Reset-1500 to 1500 units