 The OMEGA™ HX94B Series temperature/relative humidity transmitter provides a linearized and temperature compensated output signal of 4 to 20 mA, 0 to 1 Vdc, 0 to 5 Vdc or 0 to 10 Vdc depending upon the model selected for both temperature/relative humidity measurement. The output signals have been calibrated and scaled to 0 to 100°C for temperature and 0 to 100% for relative humidity. The digital temperature and relative humidity sensor is protected by a stainless steel cap that is easily removed for cleaning. The NEMA 4 stainless steel enclosure and cable entry connection provides weather tight protection. The stainless steel enclosure terminates to a 6 feet shielded cable. The cable end is either stripped leads or terminates to a 4-pin connector.

• RoHS Certified
• Accurate to ±2.5% Relative Humidity and ±0.6°C (±1°F) Temperature
• Two Separate Analog Outputs, Humidity and Temperature
• Four Analog Outputs available, 4 to 20 mA, 0 to 1V, 0 to 5V, 0 to 10V
Weight200 g (7 oz) with mounting kit
Dimensions258 L x ø19 mm OD (10.15 x 0.75")
HX94B**1.8 m (6') 4 conductor PTFE shielded cable with a 4-pin connector termination; a 4-pin mating connector is included that accepts 18 to 26 AWG wire
HX94B**W, HX94B**NPT:1.8 m (6') 4 conductor PTFE shielded cable with stripped leads termination
Electrical Connections
Enclosure Housing316 stainless steel, NEMA 4; non-NPT version includes IP68-rated cable gland
Sensor TypeDigital sensor
Max Load Resistance1.25K (for all voltage outputs)
Max Current Loop ResistanceΩ = [(V supply - 4V)/0.02A)] -50; 200Ω @ 9V supply or 1250Ω @ 30V supply
Input Power Supply9 to 30 Vdc @ 100 mA: 4 to 20 mA, 0 to 1V, 0 to 5V output, 12 to 30 Vdc @ 100 mA: 0 to 10V output
Analog Outputs for Temperature and Humidity4 to 20 mA, 0 to 1V, 0 to 5V, 0 to 10V
Operating Temperature Range0 to 100°C (32 to 212°F)
Sample Rate1 sample every 4 seconds
Response Time8 seconds typical
Repeatability±0.1%RH
Hysteresis±1%RH
Accuracy±2.5 % from 20 to 80% RH, ±3.5% from 5 to 20% and 80 to 95% RH, ±4% from 0 to 5% and 95 to 100% RH
Measuring Range0 to 100% RH
Relative Humidity
Sample Rate1 sample every 4 seconds
Response Time5 seconds minimum, 30 seconds maximum
Repeatability±0.2°C (0.4°F)
HX94BC,HX94BCNPT,HX94BCW±1.2°C from 0 to 50°C (32 to 122°F); ±1.9°C from -30 to 0°C (-22 to 32°F) and 50 to 75°C (122 to 167°F)
Accuracy±0.6°C from 0 to 50°C (32 to 122°F), ±1.25°C from 50 to 100°C (122 to 212°F), for all models except:
Measuring Range0 to 100°C (32°F to 212°F)
Temperature