 Advanced Features

Programmable via detachable display front, process calibration, signal and relay simulation, password protection, error diagnostics and selection of help text in several languages.
Application
• Linearized, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a standard analog current/voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
• Power supply and signal isolator for 2-wire transmitters. Process control with 2 pairs of potential-free relay contacts and analog output.
• Galvanic separation of analog signals and measurement of floating signals.
• The DRST-UR is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
Technical Characteristics
• When DRST-UR is used in combination with the DRSL-DISPLAY programming front, all operational parameters can be modified to suit any application. As the DRST-UR is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
• A green/red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
• A continuous check of vital stored data for safety reasons.
• 4-port 2.3 kVAC galvanic isolation.
 
• Input for RTD, TC, O, potentiometer, mA and V
• 2-wire supply 16 V
•  UL and cUL Approval
• Output for current, voltage and 2 relays
Storage Temperature-20 to 85°C
Operating Temperature-20 to 60°C
Environmental Conditions
Load Stability≤ 0.01% of span/100 Ω
Load (@ Current Output)≤ 800 Ω
Programmable Signal Ranges0 to 20/4 to 20/20 to 0/20 to 4 mA
Measurement Range0 to 12 Vdc
Voltage Input
Break 4 to 20 mAYes
Input ResistanceNom. 20 Ω + PTC 50 Ω Sensor Error Detection: Loop
Programmable Measurement Ranges0 to 20 and 4 to 20 mA
Measurement Range0 to 20 mA
Current Input
Detecting/ElseNom. 2 µA / 0 µA
Sensor Error CurrentWhen
Sensor Error DetectionYes
∆tInternal temp.-ambient temp.
CJC via int. Mounted Sensor±(2.0°C + 0.4°C * ∆t)
Cold Junction Compensation (CJC) via ext. Sensor in Connector 591020 to 28°C = ±1°C, -20 to 20°C/28 to 70°C = 2°C
Thermocouple TypeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
TC Input
Potentiometer Min/Max10 Ω to 100 kΩ
Load (@ Voltage Output)≥ 500 kΩ
Programmable Signal Ranges0/0.2 to 1; 0/1 to 5 ; 0/2 to 10; 1 to 0.2/0; 5 to 1/0; 10 to 2/0 V
Signal Range0 to 10 Vdc
Voltage Output
Current Limt≤ 28 mA
Output Limitation, on 0 to 20 and 20 to 0 mA Signals0 to 20.5 mA
Output Limitation, on 4 to 20 and 20 to 4 mA Signals:3.8...20.5 mA
NAMUR NE43 Upscale/Downscale:23 mA/3.5 mA
Sensor Error Indication:0/3.5/23 mA/none
SILHardware assessed for use in SIL applications
ApprovalMRA000000Z
EU RO Mutual Recognition Type
DNV-GL MarineStand. f. Certific. No. 2.4
ULUL 508/C22.2 no. 14
Approvals
EACTR-CU 020/2011
LVD2014/35/EU
EMC2014/30/EU
Observed Authority Requirements
Max. AC Power500 VA
Max. Current:2 AAC or 1 ADC
Max. Voltage250 VRMS
Relay FunctionsSetpoint, Window, Sensor error, Latch, Power and Off
Relay Output
Linear Resistance Min/Max0 to 10000 Ω Potentiometer Input
Linear Resistance Input
Short Circuit Detection< 15 Ω
Sensor Error DetectionYes
Effect of Sensor Cable Resistance (3/4-wire)< 0.002 Ω/Ω
Sensor CurrentNom. 0.2 mA
Cable Resistance per Wire50 Ω (max.)
RTD TypePt10/20/50/100/200/250;
Pt300/400/500/1000;
Ni50/100/120/1000;
Cu10/20/50/100
RTD input
Input Specifications
Extended EMC Immunity: NAMUR NE21, A Criterion, Burst< ±1% of span
EMC Immunity Influence< ±0.5% of span
AccuracyBetter than 0.1% of sel. range
Signal/Noise RatioMin. 60 dB (0 to 100 kHz)
ProgrammingCommunication enabler DRSL-DISPLAY
2-w. supply (term. 44...43)25 to 16 Vdc / 0 to 20 mA
Auxiliary Supplies
mA/V Input (0 to 90%, 100 to 10%)400 ms
Temperature Input (0 to 90%, 100 to 10%)1 s
Response Time
Isolation Voltage, Test/Working2.3 k Vac/250 Vac
Isolation Voltage
Max. Required Power2.5 W
Fuse400 mA SB/250 Vac
Supply Voltage, Universal21.6 to 253 Vac, 50 to 60 Hz or 19.2 to 300 Vdc
Supply
Common Specifications
13.2 to 100 Hz±0.7 g
2 to 13.2 Hz±1 mm
VibrationIEC 60068-2-6
Screw Terminal Torque0.5 Nm
Wire Size1 x 2.5 mm2 stranded wire
Weight incl. 4501 / 4511 (approx.)185 g/270 g
Weight Approx170 g
Dimensions (H x W x D) w/ 4501/4511109 x 23.5 x 116 / 131 mm
Dimensions (H x W x D)109 x 23.5 x 104 mm
Mechanical Specifications
Protection DegreeIP20
Relative Humidity< 95% RH (non-cond.)
Calibration Temperature20 to 28°C

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more