 The DRSL-SP3 bipolar isolated signal conditioner/splitter provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. Two process outputs are provided which mirror the single process input.

 
The DRSL-SP3 can be used for signal conversion of standard bipolar analog process signals into two individual unipolar or bipolar analog signals. The unit offers 4-port isolation, provides surge suppression and protects control systems from transients and noise. The DRSL-SP3 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
• Isolation and Conversion of Bipolar Process Voltage and Current Signals to Unipolar/Bipolar Signals
• Splitter Function: 1 Process Input, 2 Process Outputs
• Slimline Housing—Only 6 mm (0.24') Wide
• Multiple Signal Ranges (DIP-Switch Selectable)
Screw Terminal Torque0.5 Nm
Wire Size0.13 x 2.5 mm²/ AWG 26 to 12 stranded wire
DIN Rail TypeDIN EN 60715 - 35 mm
Weight70 g (0.15 lb) approx
Dimensions113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Mechanical
Installation AreaPollution degree 2 and measurement/overvoltage category II
Protection DegreeIP20
Relative Humidity0 to 95% RH non-condensing
Calibration Temperature20 to 28°C (68 to 82°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Operating Temperature-25 to 70°C (-13 to 158°F)
Environmental
NAMUR NE 21, A Criterion, Burst<±1% of span
Extended EMC Immunity
EMC Immunity Influence<±0.5% of span
Temperature Coefficient<±0.01% of span/°C
Accuracy<±0.05% of span
SpanCorresponds to the presently selected DIP switch output range
Response Time (0 to 90%, 100 to 10%)<7 ms or <44 ms
Cut-Off Frequency (3 dB)>100 Hz or 10 Hz (selectable via DIP-switch)
Signal/Noise Ratio>60 dB
MTBF>187 years, according to IEC 61709 (SN29500)
Isolation Voltage (Working)300 Vac
Isolation Voltage (Test)2.5 kVac
IsolationInput/output 1/ output 2/supply
Internal Consumption0.4 W typical/0.65 W max
Power Consumption0.8 W max
Supply Voltage (via Power Rail or Connectors)16.8 to 31.2 Vdc
General
Load>10 kΩ min
Functional Range0 to 11.5V
Programmable Signal Ranges0 to 10V, 2 to 10V, 0 to 5V, 1 to 5V
Voltage Output
Current Limit≤28 mA
Load Stability≤0.002% of span (presently selected range)/100 Ω
Load23 mA/300 Ω max (per channel)
Functional Range0 to 23 mA
Programmable Signal Ranges0 to 20 mA, 4 to 20 mA, ±10 mA, ±20 mA
Current Output
No. of Outputs2
Output
Input Resistance≥1 MΩ
Functional Range-11.5 to 11.5V
Programmable Ranges±5V, ±10V
Voltage Input
Input Voltage Drop<1V @ 23 mA
Current Input-23 to 23 mA
Functional Range,
Programmable Measurement Ranges±10 mA, ±20 mA
Current Input
Input

Request a Calibration Quote