Skip to main content
Press Enter
OMEGA

DRSL-RTD-LP Non Isolated Loop Powered DIN Rail RTD input Conditioner

RTD Input Non-Isolated DIN Rail Loop-Powered Signal Conditioner

Have questions? We're here to help!
Have questions? We're here to help!

 The DRSL-RTD-LP RTD input non-isolated DIN rail loop-powered signal conditioner measures a standard 2-, 3- or 4-wire Pt100 temperature sensor and provides a passive analog current output signal. The DRSL-RTD-LP provides a competitive choice in terms of both price and technology for interfacing RTD signals to SCADA systems or PLC equipment. This unit is powered by the host (output) current signal loop. Low power consumption facilitates DIN rail mounting without the need for any air gap. Easy configuration of more than 1000 factory calibrated measurement ranges is done via DIP-switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

• 2, 3 or 4-Wire Pt100 RTD Input
• Powered By the Host (Output) Current Signal Loop
• High Accuracy Better Than 0.2°C or 0.1% of Selected Range
• Slimline 6 mm (0.24') Housing
Signal/Noise Ratio>60 dB
Internal Consumption0.65 W max
Power Consumption1 W max
Voltage Drop3.3 Vdc
Supply Voltage3.3 to 35 Vdc
General
Load Stability≤0.01% of span/100Ω
Load Resistance (Ω)≤(Vsupply -3.3)/ 0.023
Output Error LevelDIP switch selectable for upscale or downscale
Screw Terminal Torque0.5 Nm
Wire Size0.13 x 2.5 mm²/AWG 26 to 12 stranded wire
DIN Rail TypeDIN EN 60715 - 35 mm
Weight70 g (0.15 lb) approx
Dimensions113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Mechanical
Installation AreaPollution degree 2 and measurement/overvoltage category II
Protection DegreeIP20
Relative Humidity0 to 95% RH non-condensing
Calibration Temperature20 to 28°C (68 to 82°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Operating Temperature-25 to 70°C (-13 to 158°F)
Environmental
NAMUR NE 21, A Criterion, Burst<±1% of span (span = selected input range)
Extended EMC Immunity
EMC Immunity Influence<±0.5% of span
Temperature Coefficient≤±0.02°C/°C
AccuracyBetter than 0.2°C or ±0.1% of selected range
Response Time (0 to 90%, 100 to 10%)<30 ms/300 ms (selectable, provides either fast response or signal dampening as needed).
Incorrect DIP-Switch Setting IdentificationBelow 3.5 mA or above 23 mA
Sensor Error Detection (Dip Switch Selectable for Enable or None)Below 3.5 mA or above 23 mA
Range Limits (NAMUR NE43 Out of Range)Below 3.8 mA or above 20.5 mA
Programmable Signal Ranges0 to 20 mA and 4 to 20 mA
Current Output
Output
Shorted Sensor Detection<18Ω
Broken Sensor Detection>800Ω
Effect of Sensor Cable Resistance (3 or 4-wire RTD)<0.002Ω/Ω
Sensor Cable Specifications50Ω per wire or 50 nF
Sensor Current, RTD<150 µA
Temperature Range-200 to 850°C (-328 to 1562°F)
Input Type2, 3, or 4-wire Pt100 RTD
Input