Skip to main content
Press Enter
OMEGA

DRSL-LPO-1 DIN Rail Output Loop Powered Isolators w/ 1 or 2 Channel Models

DIN Rail 2-Wire Transmitter Isolators

Have questions? We're here to help!
Have questions? We're here to help!

 The DRSL-LPO Series DIN rail 2-wire transmitter isolators provide a competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment. These units provide isolation and 1:1 conversion of standard current signals and are powered by the host (output) current signal loop. Input transmitter (Tx) power supply of 3.5 to 32.5V is provided.

 
The DRSL-LPO series offers isolation between input and output, provides surge suppression and protects control systems from transients and noise. These units also eliminate ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Measurement ranges are factory calibrated. These isolators operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
• 1 Channel (DRSL-LPO-1) or 2 Channel (DRSL-LPO-2) 2-Wire Transmitter Isolators
• Powered By the Host (Output) Current Signal Loop
• 1:1 Signal Ratio
• Low Channel Voltage Drop
Response Time (0 to 90%, 100 to 10%)<5 ms
Cut-Off Frequency (3 dB)100 Hz
Signal/Noise Ratio>60 dB
Isolation Voltage (Working)300 Vac
Isolation Voltage (Test)2.5 kVac
Voltage Drop (Input to Output)2.5V typical
Internal Consumption50 mW per channel
Supply Voltage6 to 35 Vdc
General
Output Overload50 mA max
Output Loop Current Limitation24 mA typical
Current Output
Available 2-Wire Transmitter (Tx) Supply3.5 to 32.5V
Functional Range3.5 to 23 mA (NAMUR NE43 compliant)
Signal Cconversion1:1
Signal Range (Input to Output)3.8 to 20.5 mA
Current Input
DRSL-LPO-22
DRSL-LPO-11
Number of Channels
Screw Terminal Torque0.5 Nm
Wire Size0.13 x 2.5 mm²/ AWG 26 to 12 stranded wire
DIN Rail TypeDIN EN 60715 - 35 mm
Weight70 g (0.15 lb) approx
Dimensions113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Mechanical
Installation AreaPollution degree 2 and measurement/overvoltage category II
Protection DegreeIP20
Relative Humidity0 to 95% RH non-condensing
Calibration Temperature20 to 28°C (68 to 82°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Operating Temperature-25 to 70°C (-13 to 158°F)
Environmental
Extended EMC Immunity NAMUR NE 21, A Criterion, Burst<±1% of span
EMC Immunity Influence<±0.5% of span (4 to 20 mA)
Temperature Coefficient (<25°C)≤±0.07 µA [(T-25°C) x Vsupply]
Temperature Coefficient (>25°C)≤±0.02 µA [(T-25°C) x Vsupply]
Absolute Accuracy (at 25°C)≤±8 µA

Accessories

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more