Skip to main content
Press Enter
OMEGA

DRS:-SP1 DIN Rail Isolator Repeater/Splitter for Current Signals

Isolated DIN Rail Repeater/Splitter for Current Signals

Have questions? We're here to help!
Have questions? We're here to help!

 The DRSL-SP1 isolated repeater/ splitter provides a competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment. Two current outputs are provided which mirror the single current input.

 
The DRSL-SP1 can be used for signal conversion of a standard process current signal into two individual analog signals. The unit offers 4-port isolation, provides surge suppression and protects control systems from transients and noise. The DRSL-SP1 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Measurement ranges are factory calibrated. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
• Isolation and Conversion of Current Signals
• Splitter Function: 1 Current Input—2 Current Outputs
• Slimline Housing—Only 6 mm (0.24') Wide
• Fast Response Time <7 ms
Screw Terminal Torque0.5 Nm
Wire Size0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
DIN Rail TypeDIN EN 60715 - 35 mm
Weight70 g (0.15 lb) approx
Dimensions113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Mechanical
Installation AreaPollution degree 2 and measurement/overvoltage category II
Protection DegreeIP20
Relative Humidity0 to 95% RH non-condensing
Calibration Temperature20 to 28°C (68 to 82°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Operating Temperature-25 to 70°C (-13 to 158°F)
Environmental
NAMUR NE 21, A Criterion, Burst<±1% of span
Extended EMC Immunity
EMC Immunity Influence< ±0.5% of span
Temperature Coefficient<±0.01% of span/°C
Accuracy< ±0.05% of span
Response Time (0 to 90%, 100 to 10%)<7 ms
Signal/Noise Ratio60 dB
Isolation Voltage (working)300 Vac
Isolation Voltage (Test)2.5 kVac
IsolationInput/output 1/ output 2/supply
Internal Consumption0.4 W typical/0.65 W max
Power Consumption0.8 W max
GeneralSupply Voltage (via Power Rail or Connectors)
Current Limit≤28 mA
Load Stability≤0.01% of span/100 Ω (span = 0 to 20 mA)
Load23 mA/300 Ω maximum
Signal Range0 to 20.5 mA (span)
Number of Outputs2
Current Output
Input Voltage Drop<1.5 Vdc
Functional Range0 to 23 mA
Measurement Range0 to 20.5 mA
Current Input