Skip to main content
Press Enter
OMEGA

DPI32-AL Iseries 1/32, 16, 1/8 DIN, Temp/Process Meters w/Alarm Outputs

iSeries 1/32, 16, 1/8 DIN, Temperature/Process Meters with Alarm Outputs

Have questions? We're here to help!
Have questions? We're here to help!

 The OMEGA™ iSeries meters with alarms offer flexibility in process measurement and alarm applications, accepting 10 different thermocouple types, 18 RTD combinations or 4 process voltage/ current inputs and providing 2 relay alarm outputs and a large multicolor, programmable display. Easily configured options include 11 different alarm conditions. Front panel configuration buttons allow the user to select the type of input, the alarm conditions and the resulting display color. Process inputs are fully scalable, supporting virtually all engineering units with a selectable decimal point providing a perfect solution for pressure, flow or other process inputs.Standard features include a built-in 24 Vdc excitation source for transmitters or other devices and a universal power supply that accepts 90 to 240 Vac. A low power option is available that supports 24 Vac or 12 to 36 Vdc.

• CE, UL Rated
• Universal Inputs
• High Accuracy
• 2 Relay Alarm Outputs
Input TypesThermocouple, RTD, analog voltage, analog current
Accuracy±0.5°C temperature; 0.03% rdg
Temperature Stability
RTD0.04°C/°C
Thermocouple @ 25°C (77°F)0.05°C/°C, cold junction compensation
Process50 ppm/°C
Reading Rate3 samples/s
Display
1/8 DINSingle 4-digit 9-segment LED 21 mm (0.83")
1/32, 1/16 DIN10.2 mm (0.40")
Thermocouple Types (ITS 90):J, K, T, E, R, S, B, C, N, L (J DIN)
Thermocouple Lead Resistance100 ? maximum
RTD Input (ITS 68)100/500/1000 ? Pt sensor, 2-, 3- or 4-wire; 0.00385 or 0.00392 curve)
Voltage Input0 to 100 mV, 0 to 1V, 0 to 10 Vdc
Input Impedance10 M? for 100 mV, 1 M? for 1 or 10 Vdc
Current Input0 to 20 mA (5 ? shunt)
Excitation
Voltage Excitation24 Vdc @ 25 mA (not available with low power option)
Alarm 1 and 2 Outputs
RelaySPDT, 250 Vac or 30 Vdc @ 3 A (resistive load)
OperationHigh/low, above/below, band, latch/unlatch, normally open/ normally closed and process/deviation; front panel configurations
General
Power90 to 240 Vac ±10%, 50 to 400 Hz, 110 to 375 Vdc, equivalent voltage
Low Voltage Power Option24 Vac, 12 to 36 Vdc; external power source must meet safety agency approvals
Operating Temperature0 to 55°C (32 to 131°F); 90% RH non-condensing
Protection
1/8 DINNEMA 1/Type 1 front bezel
1/32, 1/16 DINNEMA 4X/Type 4 (IP65) front bezel
Dimensions
1/8 DIN48 H x 96 W x 127 mm D (1.89 x 3.78 x 5")
1/16 DIN48 H x 48 W x 127 mm D (1.89 x 1.89 x 5")
1/32 DIN25.4 H x 48 W x 127 mm D (1.0 x 1.89 x 5")

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more