OMEGAs DP20 series new universal panel meter delivers high performance in a 1/8 DIN size for panel mount, and integration in a wide range of applications. The DP20 accepts universal inputs, including thermocouple, RTD, process (mA & Vdc), resistance, and true RMS voltage and current. By configuration, it will work as an AC and DC voltmeter (up to 600 V) and AC and DC ammeter (up to 5 A) offering application flexibility for process control and industrial requirements. A single universal power supply allows this unit to be suited for global use.
• Fast Access Menu—Front Key Access to Modify the Alarm Setpoints and Max/Min Memory
• External Control Function—Contact at Multifunctional Terminal 5 (Second Scaling, Decimal Point Change, ‘Hold’ the Reading or Activate the Max/Min Memory)
• Automatic, Power Saving Eco Mode
• Alarms 1 or 2, Independent, Configurable as Max/Min, with Setpoint and Hysteresis
| Analog Input Note | 4 to 20 mA, 0 to 10 Vdc (+15 Vdc excitation voltage configurable at terminal 5) |
| Decimal Points | Configurable |
| Digit Size | 14 mm |
| Display Range | -1999 to 9999 |
| Display Type | 3.5 Digit LED |
| Electrical Connection | Screw Terminal |
| Enclosure Ratings | IP65, NEMA Type 4 |
| Form factor | 1/8 DIN |
| Input Type | Thermocouple, RTD, Thermistor, Current, Voltage, DC or AC, Resistance, Frequency |
| Measuring Range | Thermocouple: Type K: -100 to 1350 °C;Type J: -100 to 1200 °C;Type E: -100 to 1000 °C;Type N: -100 to 1300 °C;Type L: -100 to 900 °C;Type R: 0 to 1768 °C;Type S: 0 to 1768 °C;Type T: -100 to 400 °C;Type C: 0 to 2300 °C;Type B: 700 to 1820 °C ;RTD: Pt100(3 wires): 200 to 700 °C ;Pt100(2 wires): 200 to 700 °C ;Pt500: -150 to 630 °C ;Pt1000: -190 to 630 °C ;Ni100: -60 to 180 °C ;Ni200: -60 to 120 °C ;Ni1000: -60 to 180 °C ;Resistance: 0 to 5K: from 9999 to -1999;0 to 50K: from 9999 to -1999;Potentiometers Nominal Value: 500 R to 20 K: from 9999 to -1999;Frequency: 15 Hz to 100 Hz: from 9999 to -1999; Signal Ranges: AC Voltages and AC Currents: 600 Vac, 200 Vac, 20 Vac, 2 Vac, 200 mVac, 60 mVac, 5 Aac, 20 mAac (True RMS measure) (accepts phase-neutral and phase-phase measure) ;DC Voltages and DC Currents: ± 600 Vdc, ± 200 Vdc, ± 20 Vdc, ± 2 Vdc, ± 200 mVdc, ± 60 mVdc, ± 5 Adc, ± 20 mAdc;Refer Tables for more information; Analog Input: 4 to 20 mA, 0 to 10 Vdc |
| Number of Inputs | 1 |
| Operating Temperature, Max | 50 °C |
| Operating Temperature, Min | 0 °C |
| Power Consumption | 2.5 W |
| Probe Type | Resistive ‘Pt’ Probes: Pt100 with 2 and 3 wires, Pt500, Pt1000 Resistive ‘Ni’ Probes: Ni100, Ni200, Ni1000 Resistive NTC Probes: See table at page 4 Resistive PTC Probes: Families KTY-121, KTY-210 and KTY-220 |
| Reading Rate | 3/sec |
| Resistance Measurement Range | Up to 20 KΩ |
| Response Time | <300 ms. (0 % to 99 % of signal) |
| Sampling Rate | 3 Hz (3 updates/second) |
| Sensor/Transmitter Power | 15 Vdc |
| Series ID | DP20-Series |
| Span Temperature Drift | 150 ppm/°C |
| Supply Power Note | 18 to 265 Vac/dc (isolated 1500 Veff @ 60 seconds) |
| Supply Power Type | AC/DC |
| Supply Voltage | 18 to 264 Vac/Vdc |
| Thermal Effects | 150 ppm/°C |
| Thermocouple Type | J, K, T, E, N, R, S, B, C, L |
| Weight | 150 g |
Request a Calibration Quote
We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn moreBrowse By Brands
Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more