 The DMD4380 accepts a dc voltage or current input and provides an optically isolated dc voltage or current output that is linear to the input. It provides filtering, amplifies, and converts the input signal to the selected dc voltage or current output that you select. The 3-way 1200V isolation eliminates ground loops, common mode voltages and greatly reduces noise pick-up. Standard features include a 15 Vdc loop power supply and a 20 Vdc loop supply for the output. The power supplies can also be wired to sink or source which allows the DMD4380 to be used with any combination of powered or unpowered mA inputs and powered or unpowered mA outputs including passive mA devices. Features such as red and green LEDs that vary in intensity to show input and output activity and an output test button help make set-up and troubleshooting fast and easy.

• Standard DIN Rail Mounting
• Fast Setup - Over 100 I/O Ranges
• Removable Connectors
• Full 3-Way Isolation
Current0-200 uAdc to 0-50 mAdc
Bipolar Voltage±50 mVdc to ±10 Vdc
Voltage0-10 mVdc to 0-50 Vdc
Weight150 g (5.3 oz
Dimensions22.5 W x 117 H x 122 mm D (0.89 x 4.62 x 4.81') height includes connectors
ConnectionsFour 4-terminal removable connectors 14 AWG max wire size
Environmental protectionIP40
MountingMounts to standard 35 mm DIN rail
Low Voltage 'DC' Option9 to 30 Vdc or 10 to 32 Vac
Std. Power80 to 265 Vac, 50/60 Hz or 85 to 300 Vdc, 2 W maximum
Thermal StabilityBetter than ±0.02% of span per °C
Operating Temperature Range-10 to 60°C (14 to 140°F)
Isolation1200 Vrms minimum, 3-way isolation, power to input, power to output and input to output
Common Mode Rejection120 db minimum
Response Time70 ms typical
Function Test ButtonSets output to test level when pressed; adjustable 0 to 100% of span via potentiometer. Factory default is approx. 50% of span
Output Ripple<10 mV rms
Output Loop Power Supply20 Vdc nominal, regulated, 25 mAdc; max ripple, less than 10 mV RMS; may be selectively wired for sinking or sourcing
Output Zero and SpanMulti-turn potentiometers to compensate for load and lead variations, ±15% of span adjustment range typical
Output LinearityBetter than ±0.1% of span
Output Offset±100% of span in 15% increments
Compliance, Drive @ 20 mA20V,1000 Ù drive
Current0-2 mA to 0-25 mA
Bipolar Voltage (10 mA max)±5 to ±10 Vdc
Voltage (10 mA max)0-1 to 0-10 Vdc
Output RangesSwitch Selectable, Field Rangeable
Input Loop Power Supply15 Vdc ±10%, regulated, 25 mAdc; max ripple, less than 10 mV RMS may be selectively wired for sinking or sourcing
Voltage Burden1 Vdc at 20 mA
Current50Ω typical
Voltage1 MΩ minimum
Input Impedance (Voltage)
Input RangesField selectable ranges via switch settings
• Amplify , Convert, or Scale Process Signals
• Isolate Single-Ended (Common Ground) PLC Inputs
• Interface Process Signals with Panel Meters, PLCs, Recorders, Data Acquisition, DCS, and SCADA Systems
 

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more