Skip to main content
Press Enter
Starting at $1,174.40USD
Configure
Dwyer

DHII Digihelic Differential Pressure Controller

NEMA 4 housing with large & bright LCD, detachable terminal blocks reduce wiring difficulties

Starting at
$1,174.40USD
Have questions? We're here to help!
Have questions? We're here to help!
Configure

The Series DHII takes all the fabulous features of the standard Digihelic® Pressure Controller and packages them in a robust NEMA 4 (IP66) housing.

The Digihelic® II Pressure Controller combines the 2 SPDT control relays, 4 - 20 mA process output and Modbus communications with a large, brightly backlit 4 digit LCD display that can easily be seen from long distances. The electrical wiring has also been enhanced in the DHII with its detachable terminal blocks. The removable terminals allow the install to easily wire the terminal block outside the housing and then attach to the circuit board, reducing wiring difficulties and installation time on the process.

The Digihelic® II Differential Pressure Control in the new NEMA 4 (IP66) enclosure enables this product to be the perfect choice when mounting pressure controls outdoors in such applications as rooftop air handlers. This housing also makes it the ideal solution for surface mounting in clean rooms or facilities where water or a cleaning solution is utilized in maintaining plant cleanliness.

• NEMA 4 housing enables a range of uses both outdoors or indoors where water is present
• Large backlight LCD display provides local reading from a distance
• Detachable terminal blocks reduce wiring difficulties saving installation time
 

ServiceAir and non-combustible, compatible gases
Wetted MaterialsConsult factory
Housing MaterialAluminum, glass
Accuracy± 0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warmup)
Stability< ± 1% per year
Pressure LimitsRanges ≤ 2.5 in W.C. = 2 PSI; 5 in: 5 PSI; 10 in: 5 PSI; 25 in: 5 PSI; 50 in: 5 PSI, 100 in: 9 PSI
Temperature Limits32°F - 140°F (0°C - 60°C)
Compensated Temperature Limits32°F - 140°F (0°C - 60°C)
Thermal Effects0.020%/°F (0.036/°C) from 77°F (25°C)
Power RequirementsHigh voltage power = 100 VAC - 240 VAC, 50 Hz - 400 Hz or 132 VDC - 240 VDC;
Low voltage power = 24 VDC ± 20%
Power ConsumptionLow voltage power = 24 VDC - 130 mA max;
High voltage power = 100 VAC - 240 VAC, 132 VDC - 240 VDC - 7 VA max
Output Signal4 - 20 mA DC into 900 Ω max
Zero & Span AdjustmentsAccessible via menus
Response Time250 ms (dampening set to 1)
Display4 digit backlit LCD 0.6 in height. LED indicators for set point and alarm status
Electrical ConnectionsEuro type removable terminal blocks with watertight conduit fittings for 1/2 in watertight conduit
Process Connections1/8 in female NPT
Enclosure RatingDesigned to meet NEMA 4 (IP66)
Mounting OrientationMount unit in horizontal plane
Weight2 lb 10 oz (1.19 kg)
Serial CommunicationsModbus® RTU, RS485, 9600 Baud
Agency ApprovalsCE, UL
SWITCH SPECIFICATIONS
Switch Type2 SPDT relays
Electrical Rating8 A @ 240 VAC resistive
Set Point AdjustmentAdjustable via keypad on face

• Air handlers
• Clean rooms

Accessories

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more