DDD Din Mounted Digital Panel Meter

Two configurable, six-character lines, eight LED alarm indicators, and four push buttons, on a display that is smaller than 5" x 2.5"

Starting at
$643.00USD
Have questions? We're here to help!
Have questions? We're here to help!
Configure

Easy to Program

With four push buttons on the face for programming in place, and a USB port for connection to a PC running MeterView Pro software, setting up the DDD is simple.
 
Strong Face in a Durable Panel
The front face of the DDD is rated NEMA 4X, IP 65, so proper installation in a suitable panel will lead to long lasting, dependable read outs.
 
Accuracy
The DDD is accurate to ±0.03% of calibrated span, giving you a precision display of your analog sensor's output.
• 2-line, 6-character display 
• Environmentally sealed face; NEMA 4X / IP65 
• Easy 4-button programming 
• Current Inputs: 4-20 or 0-20 mA 
• Voltage Inputs: 0-5, 1-5, 0-10 VDC 
• 1 Digital Input / Input Contact 
• Current Output: Isolated 4-20 mA 
• Relay Outputs: 2 or 4 SPDT Relays 
• Up to 200 mA for powering sensor 
• Configurable High/Low alarms 
• Alternating Pump Control (with output relays) 
• Optional bright display (DBD model)
Display2 lines, 6 characters each
Top line: 0.6" (15 mm) characters
Bottom line: 0.46" (12 mm) characters
Optional Sunlight Readable Bright Display (model DBD) Display Update Speed200 ms (5 updates per second)
Accuracy± 0.03% of calibrated span
Size4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm)
Weight9.5 oz (269 g)
Supply VoltageVAC: 85 - 265
VDC: 12 - 24
Input ImpedenceVoltage Inputs: > 500 kΩ
Current Inputs: 50 - 100 Ω
SPDT Relays3 A @ 30 VDC / 125/250 VAC resistive loads
1/14 HP (≈ 50 W) @ 125/250 VAC resistive loads
Input Contact/Digital InputContact Voltage: 3.3 VDC
Digital Input Logic High: 3 - 5 VDC
Digital Input Logic Low: 0 - 1.25 VDC
Default Logic: Normally Open/Low
Front Panel ratingNEMA 4X, IP65
Storage Temperature-40° - 185°F (-40° - 85°C)
Operating temperature-40° - 149° F (-40° - 65°C)
Input Options0-20 mA, 4-20 mA
0-5 VDC, 1-5 VDC, 0-10 VDC, ± 10 VDC
Output Options2 or 4 SPDT Relays
Isolated 4-20 mA
Output Transmitter Power SupplyIsolated 24 VDC @ 40 mA
Sensor Power Supply24/10/5 VDC selectable
200 mA for VAC models
100 mA for VDC models
CEUL/C-UL Listed