CT9111 1 to 4 Channel Microprocessor-Based Circular Chart Recorder

Circular Chart Recorders, Microprocesser-Based

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!

 Supported Applications

The CT9000 Series are microprocessor-based circular chart recorders that measure, display and record from 1 to 4 process variables and trace them as analog trend lines onto 254, 280 or 305 mm (10, 11 or 12") charts. A single instrument handles temperature, level, pressure, flow, mass flow, BTUs, relative humidity and other derived variables, making it a flexible choice for process recording.

Inputs are user-configurable to connect directly to thermocouple, RTD, voltage, millivolt, milliamp or switch (contact-closure) signals. A 2-line, 40-character VFD, a 15-key keypad and up to 16 profiles make setup and day-to-day operation straightforward, while up to 4 alarms per variable provide process-high, process-low and rate alarms.

The recorder is housed with a gasketed cover, case and window to a NEMA 3 (IP54) rating and carries UL, cUL and CE marks. Warning: these products are not designed for, and should not be used for, patient-connected applications; read the manual before installing or commissioning the unit.

Operating Conditions & Performance

The universal input accepts a wide set of thermocouple types with the following ranges:

• Type J: -200 to 1200°C (-328 to 2192°F)
• Type K: -250 to 1370°C (-418 to 2498°F)
• Type E: -250 to 1000°C (-418 to 1832°F)
• Type N: -250 to 1300°C (-418 to 2372°F)
• Type T: -250 to 400°C (-418 to 752°F)
• Type R: 200 to 1700°C (392 to 3092°F)
• Type S: 250 to 1750°C (482 to 3182°F)
• Type B: 200 to 1800°C (392 to 3272°F)
• RTD: -200 to 480°C (-328 to 896°F), 100 Ω platinum

DC current inputs cover 0 to 20 mA or 4 to 20 mA with an internal 50 Ω shunt. Thermocouple accuracy is 1°C (1.8°F), chart accuracy is 0.3% of span, measurement error is ±0.025% of measurement span, and cold-junction compensation accuracy is ±0.2°C @ 25°C (±0.36°F @ 77°F). Each input is scanned at a rate of 2 scans/s, and isolation is 500 Vdc/350 Vac.

The recorder operates from 0 to 50°C (32 to 122°F) at 10 to 90% RH non-condensing, stores at -40 to 65°C (-40 to 149°F) and withstands vibration from 0.3 to 100 Hz. Power is 90 to 264 Vac, 50/60 Hz. SPDT relay contacts are rated 5 A resistive @ 115 Vac, solid-state relays provide 40 mA @ 3 Vdc or 20 mA @ 4 Vdc, and current outputs drive a 650 Ω load.

Configuration Options

Models are defined by the number of pens, the number of trend colors and the number of inputs, following the order guide CT91XX - <Number of Pens> - <Number of Colors> - <Number of Inputs>. This lets a recorder be matched precisely to how many variables must be trended and in how many colors.

Capability is then expanded through ordering suffixes, with total relays and SSRs not exceeding 8:

• -AL / -SR - 2, 4, 6 or 8 relay outputs or SSRs.
• -MA1 / -MA2 - one or two 4 to 20 mA outputs.
• -MT1 / -MT2 / -MT3 - math, totalizer, or math and totalizer.
• -EN3 - plastic window (glass is standard).

The optional math capability computes mass flow, BTUs, relative humidity and other derived variables, and four totalizers are included with up to 9 displayable digits. For additional inputs, the last digit of the base number is changed to 2, 3, 4, 6 or 8 to set the total number of inputs.

Key Product Differences

The orderable line spans one to four pens with single- or four-color recording:

• CT9111 - 1-pen, 1-color recorder with 1 input.
• CT9133 - 3-pen, 3-color recorder with 3 inputs.
• CT9144 - 4-pen, 4-color recorder with 4 inputs.
• CT9151 - 1-pen, 4-color recorder with 1 input.
• CT9162 - 2-pen, 4-color recorder with 2 inputs.
• CT9173 - 3-pen, 4-color recorder with 3 inputs.

Consumables and accessories include disposable fiber-tip pen cartridges in red, green, blue and black (for example the CT9000C-RC-GR green/red cartridge), circular chart paper in 254, 280 and 305 mm (10, 11 and 12") sizes, and CT9000-WALL wall-mounting brackets. Each recorder measures 358.65 W x 425.96 H x 196.85 mm D (14.12 x 16.77 x 7.75"), needs a 322.58 W x 322.58 mm H (12.7 x 12.7") panel cutout with 133.35 mm (5.25") depth and 63.5 mm (2.5") protrusion, and weighs 11.34 kg (25 lb).

• 1-, 2-, 3- or 4-Pen Version
• Programmable for 254, 280, 305 mm (10, 11 or 12') Charts
• Accepts Thermocouple, RTD, V, mV, mA or Switch Signals
• 40 Character Display
Accuracy± 1 °C (± 1.8 °F)
Accuracy DetailThermocouple: 1°C, Chart Accuracy: 0.3%, Chart Rotation: 0.2 minutes for 24 hours
Alarm NoteAlarm Type: Process high or low, rate rising or falling, Alarm Number: Up to 4 alarms for each of 4 process variables
ApprovalsCE
Battery Lifeup to 10 yr
Battery Size and TypeLi-ion
Chart Diameter305 mm
Chart NoteChart Messages: 12; Chart Drive: DC Stepper Motor
Chart Speed6 to 9999 Hours
CMRR>120 dB
Cold Junction Compensation 0.04°/°C deviation from 25°C
Current Measurement Range4 to 20 mA
Cutout Dimensions322.58 x 322.58 mm
DeadbandFully adjustable
Display Note2-line, 40-character VFD with 5 mm (0.21") high characters, Display Formats: 3, Operator Messages: 12, Operator Inputs: 12 Keypad: 15 keys for programming and unit operation
Display TypeVFD
Enclosure RatingsIP54, NEMA Type 3
Height425.96 mm
Input NoteInput Isolation: 350 Vac, 500 Vdc;Contact Closure: Open/closed switch sensing without external voltages or resistors;Value Cutoff: None, at Value, to Zero below value, to Zero near Zero
LED Indicators8 User Configurable, Red LED Status Indicator
Length196.85 mm
Measurement Range NoteThermocouple: J: -200 to 1200°C, K: -250 to 1370°C, E: -250 to 1000°C, N: -250 to 1300°C, T: -250 to 400°C, R: 200 to 1700°C, S: 250 to 1750°C, B: 200 to 1800°C, G: 0 to 2300°C, C: 0 to 2300°C, D: 0 to 2300°C, NNM: 0 to 1370°C, PLATINEL II: 0 to 1400°C RTD: -200 to 480°C Current: 0 to 20 mA, 4 to 20 mA Voltage: 0 to 25 mV, 0 to 100 mV, 0 to 1V, 0 to 10V
Measurement TypeThermocouple, RTD, Current, Voltage, Switch Signals
MountingPanel Mount or Wall Mounting
Mounting Orientation± 30 degrees forward/backward of vertical, ± 10 degrees side tilt from vertical
NMRR100 dB @ 60 Hz
Number of Channels1
Operating Temperature, Max50 °C
Operating Temperature, Min0 °C
Panel Depth133.35 mm
Panel Protrusion63.5 mm
Pen TypeFiber tip Marker Assembly
Power Consumption60 VA
Recording NoteRecorded Values: 20 values can be trended/recorded, Recording Methods: Drag pen simulation, instantaneous value, connect the values, average value, connect the averages\
Relative Humidity10 to 90% RH, non-condensing
RTD Type100 Ω Pt sensor; α= 0.00385
Sampling Rate2 Scans/sec
Sensor Break DetectionSensor Fault Detection: Sensor break on all T/Cs, RTDs, 1V, 1 to 5V, 4 to 20 mA and mV ranges; sensors high and low on all inputs, 5% above or below range; Sensor Break: Up-scale or down-scale
Series IDCT9000-Series
Standard Limits of ErrorError Limit: Measurement Error: ±0.025% of measurement span reference accuracy, Cold-Junction Compensation Error: ±0.2°C @ 25°C, Linearization Error: T±0.25°C typical, ±0.5°C worst case with exceptions; RTD: ±0.1°C typical, ±0.3°C worst case, Ambient Temperature Error: ±0.01% of span per °C; Measurement Error: ±0.025% of measurement span reference accuracy
Storage, Temperature, Max65 °C
Storage, Temperature, Min-40 °C
Supply Power Note90 to 264 Vac, 50/60 Hz
Supply Power TypeAC
Supply Voltage90 to 264 Vac
Temperature Measurement RangeJ: -130 to 760°C, K: -130 to 1370°C, T: -200 to 400°C, R: 0 to 1650°C, S: 0 to1649°C, B: 100 to 1824°C, RTD: -210 to 440°C
Thermocouple TypeJ, K, T, E, N, R, S, B, G, C, D
Time Accuracy1 min/month Typically, 4 min/month worst case
Vibration0.3 to 100 Hz @ 0.2 g
Voltage Measurement Range0 to 5 Vdc
Weight11.34 kg
Width358.65 mm
Wire Code Option2- or 3- Wire