Skip to main content
Press Enter
Buy now! $1,220.95USD
Dwyer

CRF2-WR01T-072 Level Transmitter

4-20 mA output, RF Admittance, Easy Calibration

Buy now!
$1,220.95USD
Have questions? We're here to help!
Have questions? We're here to help!

The Series CRF2 is a level transmitter providing a two-wire 4 to 20 mA output to indicate level of liquids, powders and bulk materials. State of the art sensing technology in the CRF2, using impulse RF admittance measurement provides excellent accuracy and stability. The CRF2 senses capacitance changes resulting from the height of the material in the tank between the probe and the tank wall. In non-metallic tanks or tanks that do not have the wall parallel to the probe a ground reference must be used.

The CRF2 comes with either a rigid or flexible probe depending on application installation need and probe length required. Featured in the CRF2 is easy push button calibration of zero and span. Custom order the CRF2 to any length probe that you need for your application. FEP covered probe is ideal for use with corrosive media. This technology also provides immunity to external RF sources like walkie-talkies and cell phones as well as minimal interference with radio communication or other electronic systems.

  • State of the art sensing technology, uses impulse RF admittance measurement which provides excellent accuracy and stability
  • Comes with either a rigid or flexible probe depending on application installation need and prove length required
  • Easy push button calibration of zero and span
  • Any length probe can be customer ordered for and specific application
  • FEP covered probe is ideal for use with corrosive media
  • Immune to external RF sources like walkie-talkies and cell phones as well as minimal interference with radio communication or other electronic system
ServiceLiquids, powders, and bulk materials compatible with wetted materials.
Wetted MaterialsStandard: rod/cable: FEP; connection: 316 SS. Ground Option: rod/cable and connection: 316 SS; cable spacers: PVC. Flange Option: material of flange.
Capacitance Range0 to 2000 pF.
Sensitivity0.15 pF.
Minimum Span8 pF.
Accuracy±0.5 pF or ±0.25% of span, whichever is greater
Repeatability±0.25 pF or ±0.1% of span, whichever is greater.
Temperature LimitsAmbient: -40 to 185°F (-40 to 85°C); Process: -40 to 250°F (-40 to 121°C).
Pressure Limit100 psi (6.9 bar)
Power Requirements12 to 35 VDC.
Output Signal4 to 20 mA or 20 to 4 mA, 2 wire.
Electrical Connection0.5 s.
Mounting OrientationScrew terminal
Conduit Connection1/2" NPT female
Process ConnectionStandard: 3/4˝ NPT male. Optional: 1˝, 1-1/2˝, NPT or BSPT, 1˝, 1-1/2˝, or 2˝ sanitary clamp, 2˝, 3˝, or 4˝ 316SS or PVC 150# flange.
Enclosure RatingNEMA 4X (IP66) weathertight/corrosion resistant.
Spark/Static Protection10 M Ohm dissipation resistance with spark gap. Surge current to 100 A max.
CalibrationZero, Span, 4mA, 20 mA
Mounting OrientationVertical
Weight6 ft rod type: 3.6 lb (1.63 kg).
  • Pulp and paper processing
  • Chemical processing
  • Food and beverage
  • Aggregates
  • Plastics
  • Mining

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more