A low voltage monitor providing automatic fan control to help maintain acceptable levels of Carbon Dioxide

Buy now!
$660.10USD
Have questions? We're here to help!
Have questions? We're here to help!

 The CD-6G  is a low voltage monitor providing automatic fan control to help maintain acceptable levels of Carbon Dioxide in greenhouses, the beverage and food industry, refrigeration, welding, pharmaceutical, and other chemical processing or other commercial applications.  Can be used as a stand-alone detector and controller and as an analog/digital transducer for use with the DVP-120 and DVP-1200 series as well as other systems.  The monitor has a high range of 0-5% by vol. (0-50,000PPM) with a recommended coverage area of 900 – 5000 sq. ft.  – ETL Listed

 • Easy installation to 4x4 electrical boxes via mud plate

• User selectable settings (Default to industry standards) via two-button interface
• 5 A SPDT fan relay, 0.5A alarm relay to control fans, valves, louvers, horn and strobes
• 4-20mA output to control VFDs and send to BMS
• LED display to show gas concentrations easily
• End of life notification 
• Field calibration kits available 
WarrantyTwo year limited warranty
CertificationsETL Listed
*See detector manual for additional certifications
Relays5A Fan relay & 0.5A alarm relay
User adjustable settings
Mounting4” x 4” electrical box
Current LoopAnalog: 4-20mA
MRS-485: Digital Modbus adapter
BRS-485: BMS communication
DisplayLED (can turn on/off)
Ambient Humidity10-90% RH non-condensing
Operating Temperature-4°F to 122°F (-20°C to 50°C)
CO2 Detectors: 32°F to 122°F (0°C to 50°C)
Voltage/Current6-Series
Power: 3 W (max) from 12 to 24 VAC or
12 to 32 VDC :Current @ 24 VDC: 75 mA in
alarm, 50 mA fan relay on and 23 mA stand by
12-Series
Power: 100-240 VAC (50 to 60 HZ)
Current: 1.0 A MAX
Weight1 pound (0.45 kg)
Size4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
• Parking garages
• Mechanical rooms
• Restaurants
• Battery charging stations 
• Breweries
• Storage facilities
• Loading docks
• Warehouses
• Firehouses & ambulance bays
• Refrigeration facilities
• Vehicle repair facilities
• Bus depots
  • Thumbnail of document CD 6 G Operation Manual Rev 1 0 1 15042
    Download

    CD 6 G Operation Manual Rev 1 0 1 15042

    Download
  • Thumbnail of document Commercial Series Data Sheet 11 16578
    Download

    Commercial Series Data Sheet 11 16578

    Download

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more