43000 Capsu-Photohelic Pressure Switch/Gage

Highly repeatable pressure switches combined with a precise pressure gage, encapsulated sensing element, easy to adjust set point indicators

This product is no longer available. Contact us at 800-567-8686 for alternative solutions.

Have questions? We're here to help!
Have questions? We're here to help!

Series 43000 Capsu-Photohelic® Switch/Gages function as versatile, highly repeatable pressure switches combined with a precise pressure gage employing the time-proven Magnehelic® gage design. The Capsu-Photohelic® switch/gage employs an encapsulated sensing element for use with both liquids and gases at pressures to 500 PSIG (34 Bar). Optional cast brass case is available for water or water based liquids. Two phototransistors actuated, DPDT relays are included for low/high limit control. Easy to adjust set point indicators are controlled by knobs located on the gage face. Individual set point deadband is one pointer width — less than 1% of full scale. Set points can be interlocked to provide variable deadband — ideal for control of pumps.

• Gage capsule permits high-pressure usage with small differentials
• Zero and range adjustments outside of gage means no disassembly in normal service
• Time-proven, simple, frictionless movement that permits full scale readings as low as 0.5 in W.C.
• Photo-electronic relays provide fast-acting switching with variable deadband control for chatter-free operation

GAGE SPECIFICATIONS
ServiceCompatible gases and liquids. Brass case option required for water based liquids
Wetted MaterialsConsult factory
Accuracy± 3% of FS at 70°F (21.1°C)
± 4% on 43215, 43220 and 43500
Pressure Limits-20 in Hg - 500 PSIG (-0.677 Bar - 34.5 Bar)
Temperature Limits20°F - 120°F (-6.67°C - 48.9°C). Low temperature option available
Process Connections1/4 in female NPT
Size4 in (101.6 mm) dial face,
5 in (127 mm) OD x 9-3/16 in (233.36 mm)
Weight5 lb. 8 oz (2.49 kg).
Brass 11 lb. 2 oz (5.05 kg)
SWITCH SPECIFICATIONS
Switch TypeEach setpoint has 2 form C relays (DPDT)
Repeatability± 1% of FS
Electrical Rating10 A @ 120 VAC, 6 A @ 240 VAC, 60 Hz res. 10 A @ 28 VDC
Electrical ConnectionsScrew terminals
Power Requirements120 VAC, 50/60 Hz; 240 VAC & 24 VAC power optional
Mounting OrientationDiaphragm in vertical position
Set Point AdjustmentAdjustable knobs on face

• Pump control
• Pumping systems
• Waste water
• Compatible liquid or gas applications

Accessories

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more