376 FC True-RMS AC/DC Clamp Meter with iFlex

Fluke connect compatible, measures up to 1000 V and 1000 A, AC or DC

Have questions? We're here to help!
Have questions? We're here to help!

The Fluke 376 FC True-rms Clamp Meter with iFlex is the most advanced troubleshooting tool for industrial and commercial electricians. The 376 is part of the Fluke Connect family of wireless test tools that enable you to log, trend and monitor measurements while remaining safely away from the arc flash zone through Bluetooth connectivity.

Find the cause of difficult problems

The 376 FC clamp meter uses an integrated low-pass filter for accurate measurements of non-linear signals, such as adjustable speed drives, electronic ballasts and other non-linear loads. The clamp also uses proprietary inrush measurement technology to filter out noise and capture motor starting current exactly as the circuit protection sees it.

Measure:

• Voltage to 1000 V AC or DC
• Resistance to 60 kΩ with continuity detection
• Min, max, average, and inrush recording to capture variations automatically
• 500 mV DC measurement range to interface with other accessories
• 1000 μF capacitance measurement
 

Work safely and conveniently

The 376 FC clamp carries a CAT III 1000 V, CAT IV 600 V safety rating, designed to offer you the highest possible protection in a test tool.

The included iFlex flexible current probe provides easier access to large conductors in tight spaces. The flexible probe:

• Expands the measurement range to 2500 A AC
• Allows frequency measurement to 500 Hz with body jaw and iFlex
 

 

• Measures AC/DC current with included iFlex current probe
• VFD low pass filter for accurate measurements of non-linear signals
• Remotely log, trend and monitor to pinpoint intermittent faults
• Inrush measurement to filter out noise and capture starting current

General Specifications

AC Current via Jaw

Range

999.9 A

Resolution 

0.1 A

Accuracy 

2% +/- 5 digits (10 Hz - 100 Hz)

2.5% +/- 5 digits (100 Hz - 500 Hz)

Crest Factor (50 / 60 Hz)

3 @ 500 A

2.5 @ 600 A

Add 2% for C.F. >2

AC Current via Flexible Current Probe

Range

2500 A

Resolution

0.1 A (≤ 600 A)

1 A (≤ 2500 A)

Accuracy

3% +/- 5 digits (5 Hz - 500 Hz)

Crest Factor (50 / 60Hz)

3.0 at 1100 A

2.5 at 1400 A

1.42 at 2500 A

Add 2% for C.F. > 2

DC Current

  • Thumbnail of document 6005995c en 370 FC series ds w 0 12423
    Download

    6005995c en 370 FC series ds w 0 12423

    Download
  • Thumbnail of document 37xfc umeng0200 12425
    Download

    37xfc umeng0200 12425

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more