1623-2 / 1623-2-KIT GEO Earth Ground Tester

Unique earth ground tester that can performs all four types of earth ground measurement

Have questions? We're here to help!
Have questions? We're here to help!

The Fluke 1623-2 GEO Earth Ground Tester offers data storage and download capabilities via USB port.  World class accessories will simplify and speed up testing time.  Model 1623-2 offers 3- and 4-pole Fall-of-Potential, earth resistance loop testing, and 4-pole Soil Resistivity testing.  Also offered is selective earth ground rod testing using 1 clamp, stakeless earth ground rod testing using 2 clamps.  This ground tester is IP56 rated for outdoor use and comes complete with a rugged carrying case and is capable of USB data storage and transfer.

Kit includes the GEO Earth Ground Tester, 2 clamps, C1620 professional carrying case, 4 earth ground stakes, and 3 cable reels.

• A unique earth ground tester that performs fast, accurate testing with and without stakes
• Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes)
• Performs selective earth ground rod testing (one clamp + stakes)
• Performs stakeless earth ground rod testing (two clamps)
• Features IP56 rating for outdoor use

Detailed Specifications

General

Display: 1999 Digit LCD

Display with special symbols, digit height 25 mm, fluorescent backlight

User Interface

Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button

Robust, Eater and Dust Resistant

Instrument is designed for tough environmental conditions (rubber protective cover, IP56)

Memory

Internal memory storage up to 1500 records accessible via USB port

Temperature Range

Temperature Range

Operating Temperature

-10°C - 50°C (14°F - 122°F)

Storage Temperature

-30°C - 60°C (-22°F - 140°F)

Temperature Coefficient

+/- 0.1% of reading/°C  < 18 °C > 28°C

Intrinsic Error

Refers to the reference temperature range and is guaranteed for 1 y

Operating Error

Refers to the operating temperature range and is guaranteed for 1 y

Climatic Class

C1 (IEC 654-1), -5°C - 45°C (23°F - 115°F), 5% - 95% RH

Protective Type

IP56 for case, IP40 for battery door according to EN60529

  • Thumbnail of document 1623 2 1625 2 Data Sheet 4463
    Download

    1623 2 1625 2 Data Sheet 4463

    Download
  • Thumbnail of document 1623 2 Manual 4464
    Download

    1623 2 Manual 4464

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more